SPC6xxx configuration: Difference between revisions
No edit summary |
No edit summary |
||
Line 29: | Line 29: | ||
<br style="clear: both" /> | <br style="clear: both" /> | ||
In accordance with the previous list the following screenshots show the proper SPC settings: | |||
[[Image:SPC_01 140226 11.31.jpg|left|thumb|400px]] | |||
[[Image:SPC_02 140226 11.32.jpg|left|thumb|400px]] | |||
[[Image:SPC_03 140226 11.32.jpg|left|thumb|400px]] | |||
<br style="clear: both" /> | <br style="clear: both" /> |
Revision as of 11:22, 26 February 2014
Language: | English • magyar |
---|
Previous chapter-> Detectomat configuration / Next chapter-> Lantronix configuration
SPC5300 and SP6xxx tool settings
The SPC6000 configuration tool is a web application that works with an Internet browser. The most common browser, Internet Explorer (IE), requires however a special setting: – In Tools, Internet Options, and then Advanced tab. In the option list, search for the Security options and enable Do not save encrypted pages to disk.
In the SPC6000 web-based configuration tool set in “Full Engineer” mode (refer to the SPC6000 documentation), note the following parameters:
- In Settings -> Comms -> Ethernet, set the SPC6000 IP addressing parameters ('IP address')
- In Settings -> Comms -> EDP, Add a receiver to the list and specify:
- Receiver ID (unique number). The Receiver ID must match the SIWENOID setting
- Network Address (IP address) of the SIWENOID server
- In Settings -> Comms -> EDP, select and Edit the receiver entry and specify:
- In the Network section, the Network port (UDP port). The Network port must match the SIWENOID setting.
- In the Event section, the Protocol version that must be Version 2
- Primary Receiver must be checked
- Requeue Event must be checked
- Event filter list must be all checked
- In Settings -> Timers, make sure that Dialer delay is set to zero, else a delay occurs before alarms get transmitted to the SIWENOID.
'Generating the SPC export file'
- In File -> Download, browse and download the file
When the web tool is connected to the SPC6000 unit in Full Engineer mode, then no alarm messages are transmitted to SIWENOID.
In accordance with the previous list the following screenshots show the proper SPC settings:



Previous chapter-> Detectomat configuration / Next chapter-> Lantronix configuration