Siwenoid v2 Aritech configuration
Language: | English • magyar |
---|
Setting up the Atc 1000 for an Aritech control panel
For communication we will need an Atc-1000 Ethernet converter with the following settings.
The default IP address for the ATC-1000 is 192.168.2.1
Connect to a computer via Ethernet, then enter the above IP address into your browser.
Fill in the required username and password fields. (Default username: admin, password: system)
Once logged in, click "UART" in the left menu and set the fields as follows:
UART settings
Mode: set to RS232
Baudrate: set to 9600
Parity Type: None
Stop Bit: 1
Hardware Flow Control: None
Port setting
To communicate with Siwenoid we will need a TCP port, which can be set in the TCP Mode menu.
The Port is set to "23" by default. If we change it, note that it will be necessary to communicate with Siwenoid.
IP-mask-gateway setting
Set the IP for the ATC according to the network segment (Siwenoid will also need this) and the network mask and gateway.
Connection between control panel and ATC-1000
Communication will require a special cable, which must be made by hand.
We will need 2 9-pin female connectors and at least 4-core cables.
The connection is shown in the following figure: