;1) Client identifier
;1) Client identifier
: Siwenoid will use this ID to log in to the SPC.
: Siwenoid will use this ID to log in to the SPC.
Line 52: Line 52:
;4) Communication ports
;4) Communication ports
: The port siwenoid and the SPC panel uses for communication. Leave it at 50000, exept if you use more SPC panels.
: The port siwenoid and the SPC panel uses for communication. Leave it at 50000, exept if you use more SPC panels.
;5) Save
;5) Always Connected
: This is required for every new EDP to keep communicating.
;6) Save
: After all settings done click on the SAVE button to acept the changes.
: After all settings done click on the SAVE button to acept the changes.


Line 60: Line 62:
On the bottom of the previous screen there is the "FiLTER" button. Click on it and setup what communications should be sent to Siwenoid.
On the bottom of the previous screen there is the "FiLTER" button. Click on it and setup what communications should be sent to Siwenoid.


All checkboxes must be marked, so the Siwenoid can receive every alert and status changes.
All checkboxes must be marked, so Siwenoid can receive every alert and status changes.
If not all boxes check, the system won't work together as intended.
If not all boxes check, the system won't work together as intended.


Line 75: Line 77:
<br style="clear: both" />
<br style="clear: both" />


=SPC5300 hozzáadása SIWENOID-hoz=
=Adding SPC5300 to SIWENOID=
==Konténer==
==Container==
Siwenoidban, kliens szotfverből adjunk hozzá az adatpont hierarchiához egy újabb Container-t (konténert, tárolót)
Open tree view in Siwenoid, and add a new container to the datapoint's database. (Right click on the tree → new container)


===SPC Konténer beállítások===
===SPC container settings===
A konténer nevét tetszőlegesen adjuk meg ''(példánkban "SPC demo")''
You can set the name of the SPC arbitrarily ''("SPC demo" in the example)''
A legördülő menüből válasszuk ki az '''SPC''' típust.  
Select the type ''SPC'' from the type list.
[[Image:Spc siwenoid configuration-09.jpg|left|thumb|500px]]
[[Image:Spc siwenoid configuration-09.jpg|left|thumb|500px]]
;1) Protokoll
;1) Protocol
: Az "EDP (UDP master)" lehetőséget válasszuk!
: Select the "EDP (UDP master)" option.
;2) Host
;2) Host
:Ide az SPC központ előzőleg beállított/ leellenőrzött IP címe kerül.
:Here you enter the IP address of the SPC panel.
;3) Port
;3) Port
:Az előző részben beállított portot írjuk be.
:Here you can add the communication port (50000 in the previous example)
;4) Local ID
;4) Local ID
: A "reciever ID" az SPC beállítássaiból. Az egyedi azonosító, amin keresztül az SPC azonosítani tudja a kezelőt. (esetünkben ez a Siwenoid lesz)
: The "reciever ID" from the SPC settings. The unique ID throught what Siwenoid can connect to the SPC.
<br />
<br />
Ha a hálózaton több SPC központ van, egyenként más portot kell beállítani nekik, hogy ne akadjon össze a kommunikáció
If there are more SPC panels on the same network, they must use different ports per spc/siwenoid container.
 
<br style="clear: both" />
<br style="clear: both" />


===Adatpontok letöltése===
===Downloading datapoints===
Ha hozzáadtuk a konténert, akkor máris böngészhetjük a központ adatpontjait.
If we added the container we can import datapoints (motion sensors, zones etc) from the SPC itself.


'''Érdemes a konténeren jobb egérgombbal kattintva megjeleníteni a felugró menüt, kikapcsolni a kommunikációt majd újra elindítani.'''
'''If the datapoints cannot be browsed right after adding the container, please disable then enable communication from popup menu of the tree view.'''


[[Image:Spc siwenoid configuration-0b.jpg|left|thumb|500px]]
[[Image:Spc siwenoid configuration-0b.jpg|left|thumb|500px]]
;1) Adatpontok beolvasása
;1) Importing datapoints
: A böngészés lehetőséggel élőben csatlkozhatunk a központra, és olvastahatjuk be az SPC-ben definiált zónákat, érzékelőket (Adatpontokat) a Siwenoidba.
: With datapoint browsing we can briowse the datapoints while the system is up and running. We can import all datapoints to Siwenoid.
<br style="clear: both" />
<br style="clear: both" />
A képen látható a panelbe integrált adatpontok és zónák nevei
You can see the (demonstarative) importable zone and datapoint names on the picture.


===Adatpontok hozzáadása===
===Ading datapoints===
Az SPC adatpontjait böngészve jobb egérgombbal kattintva hozhatjuk elő a felugró menüt.
While browsing the datapoints of the SPC panel, use right click and then click on the "import datapoints to container" text.
[[Image:SPC 15 140226 12.52.jpg|left|thumb|349px]] A menüből válasszuk az "import items to container" (elemek hozzáadása a konténerhez) lehetőséget.
[[Image:SPC 15 140226 12.52.jpg|left|thumb|349px]] The datapoints of the SPC will be imported to Siwenoid.
Ekkor az SPC-n tárolt adatpontokat a Siwenoid integrálja.
<br style="clear: both" />
 
== SPC5300 and SP6xxx tool settings ==
The SPC6000 configuration tool is a web application that works with an Internet browser. The most common browser, Internet Explorer (IE), requires however a special setting:
– In '''Tools''', '''Internet Options''', and then '''Advanced''' tab. In the option list, search for the '''Security''' options and enable '''Do not save encrypted pages to disk.'''
----
In the SPC6000 web-based configuration tool set in “Full Engineer” mode (refer to
the SPC6000 documentation), note the following parameters:
* In '''Settings -> Comms -> Ethernet''', set the SPC6000 IP addressing parameters ('IP address')
* In '''Settings -> Comms -> EDP''', '''Add''' a receiver to the list and specify:
** '''Receiver ID''' (unique number). The Receiver ID must match the SIWENOID setting
** '''Network Address''' (IP address) of the SIWENOID server
* In '''Settings -> Comms -> EDP''', select and Edit the receiver entry and specify:
** In the '''Network''' section, the '''Network port''' (UDP port). The Network port must match the SIWENOID setting.
** In the '''Event''' section, the '''Protocol version''' that must be '''Version 2'''
** '''Primary Receiver''' must be checked
** '''Requeue Event''' must be checked
** '''Event filter''' list must be all checked
* In '''Settings -> Timers''', make sure that '''Dialer delay''' is set to zero, else a delay occurs before alarms get transmitted to the SIWENOID.
<br style="clear: both" />
== Fetching SPC datapoint structure ==
[[Image:SPC_14 140226 12.46.jpg|left|thumb|400px]] Use "Browse datapoints" popup menu to get SPC structure online.
<br style="clear: both" />
[[Image:SPC_15 140226 12.52.jpg|left|thumb|400px]] Initiate import onto the SPC container by popup menu.
<br style="clear: both" />
<br style="clear: both" />
Finally restart the communication of container of SPC to get synchronized with it!


== SPC5300 and SP6xxx tool screenshots ==
== SPC5300 and SP6xxx tool screenshots ==

Latest revision as of 08:24, 7 August 2019

Language: English  • magyar

Previous chapter-> Detectomat configuration / Next chapter-> Galaxy Dimension configuration


Configuring SPC5300 from internet browser

Setting up Internet Explorer

The SPC system can only be configured from Internet Explorer. Before connecting to the SPC make sure that SSL3 encryption is enabled in the browser!

In the menu select Tools → Internet Options → Advanced tab.

In the options list find and check the SSL3 setting!


Setting up SPC for communication to Siwenoidhoz


Enter Engineer mode to setup the system (upper right corner of the screen)
In "Full Engineer" mode there are no alerts and signals sent to the event handlers! Log off as engineer after setup!

!) "Full engineer" mode, for servicing only

If we are logged in to the SPC configuration the keypad and (if configured before) Siwenoid tells us that "Engineer on site" You should click "log off" after setting up the SPC panel.


1. Ethernet settings

In menu: Communications -> Ethernet

We can setup (and double check) the Ethernet settings of the SPC.

2. EDP settings

The SPC panel must be setupped in order to communicate with the Siwenoid Server. For this we need to add a new communication channel and user for Siwenoid to handle.

After entering Full Engineer mode select Communications -> Reporting -> EDP -> Settings , or "ADD" a new one.

1) Client identifier
Siwenoid will use this ID to log in to the SPC.
2) Sending commands
We want to send commands to the SPC, so leave this checked.
3) IP Address of the Siwenoid Server
The "client" of the SPC is the Siwenoid server itself.
4) Communication ports
The port siwenoid and the SPC panel uses for communication. Leave it at 50000, exept if you use more SPC panels.
5) Always Connected
This is required for every new EDP to keep communicating.
6) Save
After all settings done click on the SAVE button to acept the changes.

The SPC is ready to communicate with Siwenoid.

EDP EVENT FILTER

On the bottom of the previous screen there is the "FiLTER" button. Click on it and setup what communications should be sent to Siwenoid.

All checkboxes must be marked, so Siwenoid can receive every alert and status changes. If not all boxes check, the system won't work together as intended.


Setting up event timers

By default the SPC panel sends messages with 30 seconds delay. For siwenoid to work correctly we must change this setting.

Search for the system timers menu

Click on Configuration (1) → System (2) → System Timers (3) → Dialer Delay (4). Check here (and correct if not) that the Dialer Delay setting must be 0 second.


Adding SPC5300 to SIWENOID

Container

Open tree view in Siwenoid, and add a new container to the datapoint's database. (Right click on the tree → new container)

SPC container settings

You can set the name of the SPC arbitrarily ("SPC demo" in the example) Select the type SPC from the type list.

1) Protocol
Select the "EDP (UDP master)" option.
2) Host
Here you enter the IP address of the SPC panel.
3) Port
Here you can add the communication port (50000 in the previous example)
4) Local ID
The "reciever ID" from the SPC settings. The unique ID throught what Siwenoid can connect to the SPC.


If there are more SPC panels on the same network, they must use different ports per spc/siwenoid container.


Downloading datapoints

If we added the container we can import datapoints (motion sensors, zones etc) from the SPC itself.

If the datapoints cannot be browsed right after adding the container, please disable then enable communication from popup menu of the tree view.

1) Importing datapoints
With datapoint browsing we can briowse the datapoints while the system is up and running. We can import all datapoints to Siwenoid.


↑ You can see the (demonstarative) importable zone and datapoint names on the picture.

Ading datapoints

While browsing the datapoints of the SPC panel, use right click and then click on the "import datapoints to container" text.

The datapoints of the SPC will be imported to Siwenoid.


SPC5300 and SP6xxx tool screenshots


When the web tool is connected to the SPC6000 unit in Full Engineer mode, then no alarm messages are transmitted to SIWENOID.



In accordance with the first section, the following screenshots show the proper SPC settings:


Remember to leave "full engineering" mode otherwise alarms are disabled to be transmitted.


This also warns that no message transmitted in "full engineering".


These SIWENOID parameters correspond with the SPC settings above.