Previous chapter-> Lantronix configuration / Next chapter-> CCTV configuration


SPC5300 and SP6xxx tool settings

The SPC6000 configuration tool is a web application that works with an Internet browser. The most common browser, Internet Explorer (IE), requires however a special setting: – In 'Tools', 'Internet Options', and then 'Advanced' tab. In the option list, search for the 'Security' options and enable 'Do not save encrypted pages to disk.'


In the SPC6000 web-based configuration tool set in “Full Engineer” mode (refer to the SPC6000 documentation), note the following parameters:

  • In 'Settings -> Comms -> Ethernet',

set the SPC6000 IP addressing parameters ('IP address').

  • In 'Settings -> Comms -> EDP',

'Add' a receiver to the list and specify:

    • 'Receiver ID' (unique number). The Receiver ID must match the SIWENOID setting.
    • 'Network Address' (IP address) of the SIWENOID server
  • In 'Settings -> Comms -> EDP',

select and Edit the receiver entry and specify:

    • In the 'Network' section, the 'Network port' (UDP port). The Network port must match the SIWENOID setting.
    • In the 'Event' section, the 'Protocol version' that must be 'Version 2'
    • 'Primary Receiver' must be checked
    • 'Requeue Event' must be checked
    • 'Event filter' list must be all checked
  • In 'Settings -> Timers', make sure that 'Dialer delay' is set to zero, else a delay occurs before alarms

get transmitted to the SIWENOID. 'Generating the SPC export file'

  • In 'File -> Download',

Browse and download the file


When the web tool is connected to the SPC6000 unit in Full Engineer mode, then no alarm messages are transmitted to SIWENOID.