SPC6xxx configuration: Difference between revisions
No edit summary |
No edit summary |
||
Line 6: | Line 6: | ||
== SPC5300 and SP6xxx tool settings == | == SPC5300 and SP6xxx tool settings == | ||
The SPC6000 configuration tool is a web application that works with an Internet browser. The most common browser, Internet Explorer (IE), requires however a special setting: | The SPC6000 configuration tool is a web application that works with an Internet browser. The most common browser, Internet Explorer (IE), requires however a special setting: | ||
– In 'Tools', 'Internet Options', and then 'Advanced' tab. In the option list, | – In '''Tools''', '''Internet Options''', and then '''Advanced''' tab. In the option list, | ||
search for the 'Security' options and enable 'Do not save encrypted pages | search for the '''Security''' options and enable '''Do not save encrypted pages | ||
to disk.' | to disk.''' | ||
---- | ---- | ||
In the SPC6000 web-based configuration tool set in “Full Engineer” mode (refer to | In the SPC6000 web-based configuration tool set in “Full Engineer” mode (refer to | ||
the SPC6000 documentation), note the following parameters: | the SPC6000 documentation), note the following parameters: | ||
* In 'Settings -> Comms -> Ethernet', | * In '''Settings -> Comms -> Ethernet''', | ||
set the SPC6000 IP addressing parameters ('IP address'). | set the SPC6000 IP addressing parameters ('IP address'). | ||
* In 'Settings -> Comms -> EDP', | * In '''Settings -> Comms -> EDP''', | ||
'Add' a receiver to the list and specify: | '''Add''' a receiver to the list and specify: | ||
** 'Receiver ID' (unique number). The Receiver ID must match the SIWENOID setting. | ** '''Receiver ID''' (unique number). The Receiver ID must match the SIWENOID setting. | ||
** 'Network Address' (IP address) of the SIWENOID server | ** '''Network Address''' (IP address) of the SIWENOID server | ||
* In 'Settings -> Comms -> EDP', | * In '''Settings -> Comms -> EDP''', | ||
select and Edit the receiver entry and specify: | select and Edit the receiver entry and specify: | ||
** In the 'Network' section, the 'Network port' (UDP port). The Network port must match the SIWENOID setting. | ** In the '''Network''' section, the '''Network port''' (UDP port). The Network port must match the SIWENOID setting. | ||
** In the 'Event' section, the 'Protocol version' that must be 'Version 2' | ** In the '''Event''' section, the '''Protocol version''' that must be '''Version 2''' | ||
** 'Primary Receiver' must be checked | ** '''Primary Receiver''' must be checked | ||
** 'Requeue Event' must be checked | ** '''Requeue Event''' must be checked | ||
** 'Event filter' list must be all checked | ** '''Event filter''' list must be all checked | ||
* In 'Settings -> Timers', make sure that 'Dialer delay' is set to zero, else a delay occurs before alarms | * In '''Settings -> Timers''', make sure that '''Dialer delay''' is set to zero, else a delay occurs before alarms | ||
get transmitted to the SIWENOID. | get transmitted to the SIWENOID. | ||
'Generating the SPC export file' | 'Generating the SPC export file' | ||
* In 'File -> Download', | * In '''File -> Download''', | ||
Browse and download the file | Browse and download the file | ||
---- | ---- |
Revision as of 15:03, 6 January 2014
Language: | English • magyar |
---|
Previous chapter-> Lantronix configuration / Next chapter-> CCTV configuration
SPC5300 and SP6xxx tool settings
The SPC6000 configuration tool is a web application that works with an Internet browser. The most common browser, Internet Explorer (IE), requires however a special setting: – In Tools, Internet Options, and then Advanced tab. In the option list, search for the Security options and enable Do not save encrypted pages to disk.
In the SPC6000 web-based configuration tool set in “Full Engineer” mode (refer to the SPC6000 documentation), note the following parameters:
- In Settings -> Comms -> Ethernet,
set the SPC6000 IP addressing parameters ('IP address').
- In Settings -> Comms -> EDP,
Add a receiver to the list and specify:
- Receiver ID (unique number). The Receiver ID must match the SIWENOID setting.
- Network Address (IP address) of the SIWENOID server
- In Settings -> Comms -> EDP,
select and Edit the receiver entry and specify:
- In the Network section, the Network port (UDP port). The Network port must match the SIWENOID setting.
- In the Event section, the Protocol version that must be Version 2
- Primary Receiver must be checked
- Requeue Event must be checked
- Event filter list must be all checked
- In Settings -> Timers, make sure that Dialer delay is set to zero, else a delay occurs before alarms
get transmitted to the SIWENOID. 'Generating the SPC export file'
- In File -> Download,
Browse and download the file
When the web tool is connected to the SPC6000 unit in Full Engineer mode, then no alarm messages are transmitted to SIWENOID.
Previous chapter-> Project backup/restore / Next chapter-> CCTV configuration