CerberusPro configuration

From Siwenoid Wiki
Revision as of 13:31, 11 December 2014 by SWNadmin2 (talk | contribs)
Jump to navigation Jump to search
Language: English  • magyar

Previous chapter-> Project backup/restore / Next chapter-> Detectomat configuration


Configuring CerberusPro

CerberusPro (SIEMENS) control unit uses Bacnet protocol to communicate with Siwenoid. Communication settings can be done in FXS72xx editor of CerberusPro control unit.

Open network settings of a CerberusPro site. In this tutorial we discuss a basic configuration when a SIWENOID and a CerberusPro control unit are in the same network segment.


First check global BACnet configuration. These settings should be used for proper communication.


BACnet device ID is the SIWENOID (as a BACnet client) address. This address has to be set in SIWENOID container definition.