Configuring CerberusPro

CerberusPro (SIEMENS) control unit uses Bacnet protocol to communicate with Siwenoid. Communication settings can be done in FXS72xx editor of CerberusPro control unit.

Open network settings of a CerberusPro site. In this tutorial we discuss a basic configuration when a SIWENOID and a CerberusPro control unit are in the same network segment.


First check global BACnet configuration. These settings should be used for proper communication.


BACnet device ID is the SIWENOID (as a BACnet client) address. This address has to be set in SIWENOID container definition.


Set the IP address of your control unit. This parameter should also be set in SIWENOID container definition.


Set the netmask of control unit ethernet interface. SIWENOID should be in the same network segment as control unit is.


This address field is the BACnet address of CerberusPro control unit. This is important when you import SibX file into SIWENOID.


Leave this settings default in most case. (When control unit and SIWENOID are not in the same network segment then BBMD should be used.)


Configuring SIWENOID

Create a new container in SIWENOID. Select control unit type, and select protocol. There are different protocol for <MP5 and >MP5. Be sure to use the appropriate. Host address is the address of CerberusPro control unit. Subnet is the network mask of BACnet protocol. 47808 is the default BACnet port number. Local address can be used only if your computer has more than one ethernet interface. Normally it should be left empty. Local Device ID is the SIWENOID (as a BACnet client) BACnet ID. This should align the settings of CerberusPro FSX72xx editor parameters.


Finally import SibX file into SIWENOID.


Previous chapter-> Project backup/restore / Next chapter-> Detectomat configuration