CerberusPro configuration: Difference between revisions

From Siwenoid Wiki
Jump to navigation Jump to search
No edit summary
No edit summary
Line 12: Line 12:
<br style="clear: both" />
<br style="clear: both" />
[[Image:_sinteso_1_Bacnet_client_config.png|left|thumb|700px]] BACnet device ID is the SIWENOID (as a BACnet client) address. This address has to be set in SIWENOID container definition.
[[Image:_sinteso_1_Bacnet_client_config.png|left|thumb|700px]] BACnet device ID is the SIWENOID (as a BACnet client) address. This address has to be set in SIWENOID container definition.
<br style="clear: both" />
[[Image:_sinteso_1_FC_ethernet.png|left|thumb|300px]] Set the IP address of your control unit. This parameter should also be set in SIWENOID container definition.
<br style="clear: both" />
[[Image:_sinteso_1_Ethernet_subnet.png|left|thumb|300px]] Set the netmask of control unit ethernet interface. SIWENOID should be in the same network segment as control unit is.
<br style="clear: both" />
[[Image:_sinteso_1_Bacnet_device_object.png|left|thumb|300px]] This address field is the BACnet address of CerberusPro control unit. This is important when you import SibX file into SIWENOID.

Revision as of 13:44, 11 December 2014

Language: English  • magyar

Previous chapter-> Project backup/restore / Next chapter-> Detectomat configuration


Configuring CerberusPro

CerberusPro (SIEMENS) control unit uses Bacnet protocol to communicate with Siwenoid. Communication settings can be done in FXS72xx editor of CerberusPro control unit.

Open network settings of a CerberusPro site. In this tutorial we discuss a basic configuration when a SIWENOID and a CerberusPro control unit are in the same network segment.


First check global BACnet configuration. These settings should be used for proper communication.


BACnet device ID is the SIWENOID (as a BACnet client) address. This address has to be set in SIWENOID container definition.


Set the IP address of your control unit. This parameter should also be set in SIWENOID container definition.


Set the netmask of control unit ethernet interface. SIWENOID should be in the same network segment as control unit is.


This address field is the BACnet address of CerberusPro control unit. This is important when you import SibX file into SIWENOID.