Siwenoid v2 Minimax configuration: Difference between revisions

From Siwenoid Wiki
Jump to navigation Jump to search
No edit summary
No edit summary
Line 22: Line 22:
- Accessing an XML file on the WIN10 operating system: C:\Users\’username’\Documents\MxSysCon\MxSysCon 5.2\TempProj\’Projekt’\FMZ5000<br>
- Accessing an XML file on the WIN10 operating system: C:\Users\’username’\Documents\MxSysCon\MxSysCon 5.2\TempProj\’Projekt’\FMZ5000<br>
- Required file from FMZ5000 folder: FMZ5000.XML<br>
- Required file from FMZ5000 folder: FMZ5000.XML<br>
===ATC UART menu item setting===
Mode: RS422 <br>
Baudrate: 19200 <br>
Character Bits: 8 <br>
Parity Type: '''even''' <br>
Stop bit: 1 <br>
Hardware Flow Control: none <br>
<br style="clear: both" />
[[Image:Atckonfig.JPG]]
<br style="clear: both" />

Revision as of 12:38, 11 June 2021

Language: English  • magyar

Connecting Mobus RS422 and ATC-1000


Modbus RS422 jumpering


MxSyscon configuration (Modbus configuration, Minimax fire alarm programming interface)


XML file

MXGUARD requires an XML file to be imported. This can be extracted from MxSyscon:

- Save program with/without saving to card
- Only in this case will the program temporarily create the XML file in the path described below
- Any program changes have been made, the XML file needs to be updated
- Accessing an XML file on the WIN10 operating system: C:\Users\’username’\Documents\MxSysCon\MxSysCon 5.2\TempProj\’Projekt’\FMZ5000
- Required file from FMZ5000 folder: FMZ5000.XML

ATC UART menu item setting

Mode: RS422
Baudrate: 19200
Character Bits: 8
Parity Type: even
Stop bit: 1
Hardware Flow Control: none