Siwenoid v2 INIM PrevidiaMax Modbus configuration: Difference between revisions

From Siwenoid Wiki
Jump to navigation Jump to search
(draft 5)
(draft 6)
Line 10: Line 10:
<span style="font-size: 1em;"><strong>Port:</strong> In the case of direct ethernet connection the port number is 502. In the case of using an RS232 to TCP IP Converter, the port number can be configured in the TCP server parameters of the converter's settings.</span><br>
<span style="font-size: 1em;"><strong>Port:</strong> In the case of direct ethernet connection the port number is 502. In the case of using an RS232 to TCP IP Converter, the port number can be configured in the TCP server parameters of the converter's settings.</span><br>
<span style="font-size: 1em;"><strong>Modbus address:</strong> The Modbus address of the PrevidiaMax panel can be set in the programming software of the panel called PREVIDIA-STUDIO. (See PrevidiaMax Modbus settings below)</span><br>
<span style="font-size: 1em;"><strong>Modbus address:</strong> The Modbus address of the PrevidiaMax panel can be set in the programming software of the panel called PREVIDIA-STUDIO. (See PrevidiaMax Modbus settings below)</span><br>
<span style="font-size: 1em;"><strong>Modbus RTU:</strong> In the case of direct ethernet connection the value has to be set to <span style="color: blue;">false</span>, in the case of using an RS232 to TCP IP Converter the value has to be set to <span style="color: blue;">true</span>.</span>
<span style="font-size: 1em;"><strong>Modbus RTU:</strong> In the case of direct ethernet connection the value has to be set to <span style="color: blue;">false</span>, in the case of using an RS232 to TCP IP Converter the value has to be set to <span style="color: blue;">true</span>.</span><br>
</div>
</div>


Line 24: Line 24:
<span style="font-size: 1em;">4. Set the same Modbus address in the dropdown box (shown on the 5th image) that is set in the Siwenoid INIM PrevidiaMax container parameters.</span><br>
<span style="font-size: 1em;">4. Set the same Modbus address in the dropdown box (shown on the 5th image) that is set in the Siwenoid INIM PrevidiaMax container parameters.</span><br>
<span style="font-size: 1em;">5. Download (write) the changes to the INIM PrevidiaMax panel. (Shown on the 6th image)</span><br>
<span style="font-size: 1em;">5. Download (write) the changes to the INIM PrevidiaMax panel. (Shown on the 6th image)</span><br>
</div>
===TCP Server settings of RS232 to TCP IP Converter:===
<div style="line-height: 1.5;">
<span style="font-size: 1.2em; display: inline-block; line-height: 2.0;"><strong>Parameters:</strong></span><br>
<span style="font-size: 1em;"><strong>Bitrate:</strong> 115200 bit/s</span><br>
<span style="font-size: 1em;"><strong>Character bits (data bits):</strong> 8</span><br>
<span style="font-size: 1em;"><strong>Parity:</strong> even</span><br>
<span style="font-size: 1em;"><strong>Stop bit:</strong> 1</span><br>
<span style="font-size: 1em;"><strong>Hardware flow control:</strong> none</span><br>
</div>
</div>

Revision as of 10:09, 16 October 2023

Language: English  • magyar

Siwenoid container parameters:

Parameters:
Host IP: The IP address or hostname where the INIM PrevidiaMax panel can be found on the network.
Port: In the case of direct ethernet connection the port number is 502. In the case of using an RS232 to TCP IP Converter, the port number can be configured in the TCP server parameters of the converter's settings.
Modbus address: The Modbus address of the PrevidiaMax panel can be set in the programming software of the panel called PREVIDIA-STUDIO. (See PrevidiaMax Modbus settings below)
Modbus RTU: In the case of direct ethernet connection the value has to be set to false, in the case of using an RS232 to TCP IP Converter the value has to be set to true.


PrevidiaMax Modbus settings:

1. Navigate to the PANEL DISPLAY section in PREVIDIA-STUDIO as shown on the first 3 images.
2. Make sure the option 'Modbus Tcp Disabled' is set to Off as shown on the 4th image.
3. Click on the MODBUS Address edit sign. (Shown at the bottom of the 4th image)
4. Set the same Modbus address in the dropdown box (shown on the 5th image) that is set in the Siwenoid INIM PrevidiaMax container parameters.
5. Download (write) the changes to the INIM PrevidiaMax panel. (Shown on the 6th image)


TCP Server settings of RS232 to TCP IP Converter:

Parameters:
Bitrate: 115200 bit/s
Character bits (data bits): 8
Parity: even
Stop bit: 1
Hardware flow control: none